Sincerehope
 
Cleanroom Equipment / Fan Filter Unit
Fan Filter Unit (FFU)
Summary
FFU is a fan filter unit which suitable for turbulent or laminar flow clean room environment, it is flexible which can install on several type ceiling grid system
. Within different design, it can be upgraded or integrated into any ceiling grid system, to achieve clean room requirement up to class 1.

FFU is one of the most effective , quietest and most economical Clean Room equipment in the market , it delivers high quality air filtration and air distribution performance in Clean Room environment of semiconductor , micro-electronics , microbial industry and other occasions that need special control with dust.

Features
*Versatile and flexible, capable of supporting any Clean Room
configuration.
*Low height, its design can save space.
*Particular inside diffuser plate, equality diffuse wind pressure ,
equality and steady air velocity.
*Special inlet design can reduce pressure drop and noise ,dont need
to add sound insulation.
*High quality blower and efficiency motor, low energy consumption
reduces operating cost.
*Steady capability non-step and step transformer controller ,can be
adjusted air volume freely.

Specifications of standard models

Power Source 1230V 50/60Hz AC Motor

Motor

AC310

AC355AK

AC355AL

Module Size(Ft)

2 2

2 4

2 4

3 4

3 4

4 4

Voltage(V)

220-240

Power(W)

70

135

195

230

260

290

Height(mm)

250

250

275

275

275

350/315

Weight
(Kg)

zincification

14

25

26

40

40

55

SUS430

14

25

26

40

40

55

Aluminium

10

17

18

25

25

35

Noise(dBA)

50

52

53

53

53

55

TSP
(Pa)

@0.45m/s

230

180

250

180

260

190

@0.35m/s

240

200

310

250

290

250

@0.30m/s

245

210

325

265

305

270

 

Power Source 1230V 50/60Hz DC Motor

Motor

DC310

DC355

DC400

Module Size(Ft)

2 2

2 4

2 4

3 4

3 4

4 4

Voltage(V)

220-277

Power(W)

60

110

130

185

185

245

Height(mm)

250

250

275

275

275

350

Weight
(Kg)

zincification

14

25

26

40

41

55

SUS430

14

25

26

40

41

55

Aluminium

10

17

18

25

26

35

Noise(dBA)

50

52

53

53

54

54

TSP
(Pa)

@0.45m/s

230

180

250

180

300

250

@0.35m/s

240

200

310

250

340

320

@0.30m/s

245

210

325

265

360

350

*Special dimensions can be customized.

Optional Accessories
*Pre-filter
*Abnormal light with relay
*Running light with relay
*Abnormal and running light with relay
*Three pin plug c/w 2.5m power cable
* Three pin plug c/w socket 2.5m power cable

Installation
*Make sure FFU is vertical during transportation, unloading and loading;
*Please use forklift to unload goods;
*In order to work long time ,FFU can not install in oily &smoky,
Incensive gas, dusty, public passage or other foreign particle cumber site;
*To avoid unit get seriously rusty, never install the FFU inside the
alkaline of high salty environment ,and also inside the sulfuric acid flow environment;
*To ensure incoming air equality, please reserve enough space for air
return during FFU installation;
*FFU install with the HEPA filter on the ceiling grid.

Maintenance

*Always observe the FFU operation status, if detect the abnormal
situation, please cut off the power immediately;
*Do not disassemble electrical components.

Warning

*The workers are prohibited to step or walk on the air inlet area but they are allow to step on the borderland.
*There must be a preventive measure to avoid any air condensation liquid from wringing the FFU.
*The power input must be turned off before switching the TSC-10 speed controller.

 